- Range 40 A - 1600 A, Ics=100% Icu, three optimum frames
- Overload: Ir adjustable 0.4 to 1 x In
- tr adjustable 3 to 30 s
- Short circuit: Isd adjustable 1.5 to 10 x Ir
- tsd 0 to 0.5 s
- Inbuilt instantaneous protection Ii fixed
- Option for in-built or add-on earth leakage module: sensitivity 0.03-0.3-1-3 A, tripping 0-0.3-1-3 s
- Breaking capacity 25 kA, 36 kA, 50 kA, 70 kA & 100 kA
- Integrated energy metering with accuracy class 2
- Measures currents, voltage, frequency, power, energy and harmonics
- Internal battery with battery measure function
- Communication ready via COMM port
- Logical selectivity ready (zone selective interlocking)
- Dynamic selectivity as per selectivity charts
- In-built USB port for software diagnosis
- Suitable for isolation
Specifications
Poles: 4P | Rated current: 40 / 100 / 160 / 250 A | Breaking capacity: 25 / 36 / 50 / 70 kA