About this product
Key features
- Range 250 A - 1600 A, Ics=100% Icu, two optimum frames
- Overload: Ir adjustable 0.4 to 1 x In
- tr adjustable 3 to 30 s
- Short circuit: Isd adjustable 1.5 to 10 x Ir
- tsd 0 to 0.5 s
- Inbuilt instantaneous protection Ii fixed
- Ground fault: Ig 0.2 to 1 In & OFF
- tg 0.1 to 1 s
- Breaking capacity 36 kA, 50 kA, 70 kA & 100 kA
- Integrated energy metering with accuracy class 2
- Measures currents, voltage, frequency, power, energy and harmonics
- Internal battery with battery measure function
- Communication ready via COMM port
- Logical selectivity ready (zone selective interlocking)
- Dynamic selectivity as per selectivity charts
- In-built USB port for software diagnosis
- Switchable thermal memory
- Suitable for isolation
Specifications
Rated current range: 320 A to 1600 A (header states 250 A - 1600 A) | Protection unit: Sg (LSIg) + energy metering | Energy metering accuracy: Class 2 | Breaking capacity: 36 / 50 / 70 kA