About this product
Key features
- Fast Ethernet interface for heterogeneous network
- Processes Cerberus PRO FD720, Cerberus Nova and earlier detector series signals
- Slots for RS232 and RS485 serial interfaces
- Floor repeater displays, terminals and alarm devices on C-NET with power via C-NET
- Integrated degraded mode function
- Freely configurable time-dependent controls (weekly, monthly, yearly programs)
- Configured with Cerberus-Engineering-Tool
- Firmware updatable
- Interface to Siemens danger management system
- Networkable via C-WEB/SAFEDLINK and C-WEB/LAN
Applications
- Medium-sized industrial plants
- Regional banks
- Office complexes
- Single-sector extinguishing applications
Specifications
C-NET addresses: 504 | Integrated C-NET lines: 4 loops / 8 stubs (8 loops / 16 stubs with loop extension) | Slots for module bus cards: None | Ethernet port RJ45: 1 | Integrated RT alarm relay / RT fault relay: 1 / 1 | Monitored alarm output / monitored fault output: 1 / 1 | Horn output, monitored (with sounder module): 2/8 | Configurable inputs/outputs 24 V: 12 | Dimensions with cover cap (W x H x D): 443 x 802 x 188 mm (with cover cap) | Dimensions without cover cap (W x H x D): 430 x 796 x 165 mm | Power supply: 1 x 250 W | Max. battery capacity: 25 Ah | Degraded mode and emergency supply: Yes | Emergency operation in degraded mode: Up to 72 h (depending on configuration) | Event log: Up to 13000 events per station | Ground fault monitoring: All outgoing detector lines monitored
Standards: EN 54-2 | EN 54-4