Type 1 fire alarm cable (FFX200 05mSOZ1-R) has a plain annealed copper class 2 conductor, glass mica fire resistant tape as primary insulation and high performance silicone rubber as secondary insulation. It has a glass fiber tape, aluminium fire barrier electrostatic screen with tinned copper drain wire and an LTS3 LSZH sheath. It meets BS 7629-1 Standard 30 and Standard 60 and also Enhanced 120 when tested to BS EN 50200 and BS 8434-2.
Key features
- Low smoke zero halogen (LSZH), flame retardant
- Voltage rating 300/500 V
- Aluminium fire barrier electrostatic screen with tinned copper earth/drain wire
- Sheath type LTS3 to BS 7655 section 6.1
- Minimum bending radius 6D
- Meets category STANDARD 30, STANDARD 60 and ENHANCED 120 (BS EN 50200 / BS 8434-2)
Applications
- High rise buildings
- Commercial complexes
- Schools and educational institutions
- Hospitals
- Connection of smoke detectors, emergency lightings, exit signboards and fire command center
Specifications
Application: These cables are used in high rise buildings, commercial complexes, schools and educational institutions, hospitals, etc. for the connection with security systems like smoke detectors, emergency lightings, exit signboards and fire command center. These cables are used where the fire safety is utmost important. | Voltage Rating: 300/500V | Temperature Range: -30°C to +70°C (the cable should not be flexed when either the ambient or cable temperature is below 0°C) | Minimum Bending Radius: 6D | Core Colours: 2 Core: blue, brown; 3 Core: blue, brown, black; 4 Core: blue, brown, black, grey | Screen: Glass fiber tape; earth/drain wire of annealed tinned copper to BS EN 60228; electrostatic screen of aluminium fire barrier | Sheath: Sheath type LTS3 to BS 7655 section 6.1 | Properties: Low smoke zero halogen (LSZH), flame retardant | Code Designations: FFX - Fire Alarm Cable, 200 - 300/500 V Multicore (Type), 05 - 300/500 V (Voltage), mS - Mica Tape + Silicon Rubber, mZ - Mica Tape + Thermosetting LS0H, S - Silicon Rubber, O - Overall Aluminium screen, Z1 - LSZH, U - Solid conductor to EN 60228 class 1, R - Stranded conductor to EN 60228 class 2 | Compliance Marks: REACH, RoHS, CE | Standard: BS 7629-1, BS EN 50200 | Cable Type: Type 1 - FFX200 05mSOZ1-R - CU/MGT/SR/OSCR/LSZH 300/500V Class 2 | Conductor: Plain annealed copper conductor to BS EN 60228, class 2 | Primary Insulation: Glass mica fire resistant tape | Secondary Insulation: High performance silicone rubber; EI 2 to BS 7655 Section 1.1 | Fire Performance Tests: BS 7629-1, 300/500 V fire resistant electric cables with non corrosive gases and low emission of smoke when affected by fire. Category STANDARD 30 & STANDARD 60 when tested in accordance with BS EN 50200. Also meets category ENHANCED 120 when tested in accordance with BS EN 50200 and the 120 min survival time when tested in accordance with BS 8434-2. Meets requirement for fire resistant cables as described in clause 26 2e of BS 5839-1
Standards: BS 7629-1 | BS EN 50200 | BS 8434-2 | BS 7655 | BS 5839-1 | BS EN 60228 | REACH | RoHS | CE