Key features
- Applicable to water loop, ground water, ground loop or other water systems
- Factory charged R410A so only wiring, water pipe and duct installation needed on site
- Liquid accumulator protects compressor from refrigerant liquid attack
- Access doors in three directions for easy service
- Horizontal or vertical discharge/return configurations
Specifications
Refrigerant: R410A, factory charged | Heat exchanger: Tube in tube | Compressor: Rotary (010-050) / Scroll (060-150) | Standard controller: Wired controller MC322 with 8 m communication cable | Optional controls: Wireless remote card controller, central controller (max 64 units), Smart Commander software, Modbus BMS | Operating range - indoor air DB temperature: Cooling 16-35 °C ; heating 10-30 °C | Operating range - water inlet temperature: Cooling 13-40 °C ; heating 6-35 °C | Highest ACOP: 4.94 (MWH060DRP); national standard (GB) 4.55 | Protections: High and low pressure, water leakage, circulating water temperature | Condensate drain pipe: 20 mm (010-050 table); 20 / 34 mm (060-150 table, as printed) | ESP options (8HP-15HP): 4 ESP options