Skip to main content

About this product

PROcess FIeld BUS is a fieldbus standard for communication in automation technology, linking controllers or control systems with decentralised field devices (sensors and actuators) via a single bus cable. The DP type carries data between a controller and field devices, preferably in factory automation, while the PA type connects via a coupler or linking device for process automation, e.g. in hazardous environments. The cable has bare copper stranded conductors, foam PE insulation, aluminium Mylar foil and 65% braid screen, with PVC or PUR outer sheath options and armoured versions for direct burial. More variants (flexible, steel braid, LSZH halogen free) are available.

Key features

  • DP (22 AWG, 0.32 sq mm) and PA (18 AWG, 0.8 sq mm) types
  • Foam PE insulation, aluminium Mylar foil and 65% tinned copper (ATC) braid screen
  • Violet sheath for DP, blue sheath for PA
  • PVC or PUR outer sheath options
  • armoured (GI armour wires) versions for direct burial
  • Adapted to DIN 19245 and EN 50170
  • flame retardant to IEC 60332-1-2
  • Also available (on request per brochure): flexible-application DP/PA, steel-braid DP/PA, halogen-free LSZH sheath

Applications

  • Fieldbus communication in automation technology between controllers and decentralised field devices (sensors, actuators)
  • Factory automation (DP)
  • Process automation including hazardous environments via coupler/linking device (PA)
  • Fixed indoor installation, industrial areas and direct burial (armoured types)

Specifications

Standard: Adapted to DIN 19245 & EN 50170 | Operating Voltage: 250 V (not for power installation) | Insulation Resistance: 5000 GΩ x cm (printed as '5000 G x cm') | Minimum Bending Radius - Flexing: 12 x cable ø | Minimum Bending Radius - Fixed Installation: 6 x cable ø | Test Voltage: 1500 V | Flame Retardancy: Complies with IEC 60332-1-2 | Conductor: Bare copper stranded 7-wire conductor | DP - Conductor Resistance (loop) at 20°C: 110 Ω/km (max.) (unit printed as '/km') | DP - Mutual Capacitance: 35 nF/km (max.) | DP - Inductance: 0.65 mH/km (nom.) | DP - Characteristic Impedance / Attenuation: 9.6 kHz: 270 ± 27 Ω, ≤ 0.25 dB/100 m; 38.4 kHz: 185 ± 18.5 Ω, ≤ 0.40 dB/100 m; 4 MHz: 150 ± 15 Ω, ≤ 2.2 dB/100 m; 16 MHz: 150 ± 15 Ω, ≤ 4.2 dB/100 m | PA - Conductor Resistance (loop) at 20°C: 44 Ω/km (max.) (unit printed as '/km') | PA - Mutual Capacitance: 55 nF/km (max.) | PA - Characteristic Impedance @ 31.25 kHz: 100 ± 15 Ω | PA - Attenuation @ 39 kHz: ≤ 3 dB/km | PA - Inductance: 0.65 mH/km (nom.) | Segment Length vs Baud Rate (m / ft): 9.6 kbit/s: 1200 m / 3940 ft; 19.2 kbit/s: 1200 m / 3940 ft; 45.45 kbit/s: 1200 m / 3940 ft; 93.75 kbit/s: 1200 m / 3940 ft; 187.5 kbit/s: 1000 m / 3280 ft; 500 kbit/s: 400 m / 1310 ft; 1500 kbit/s: 200 m / 656 ft; 3000 kbit/s: 100 m / 328 ft; 6000 kbit/s: 100 m / 328 ft; 12000 kbit/s: 100 m / 328 ft | More Variants Available: DP and PA for flexible applications; DP and PA with steel braid; halogen-free variant with Low Smoke Zero Halogen (LSZH) outer sheath

Standards: DIN 19245 | EN 50170 | IEC 60332-1-2 | REACH | RoHS | CE

Request a Quote

Get bulk pricing directly from the supplier.

Login to Request Quote
WHY BUY HERE
GST verified supplier
PAN & GSTIN checked by BrickoMart
Site delivery available
Coordinated with the supplier
GST invoice on every order
Full input tax credit
Quality-checked dispatch
Sourced from verified suppliers

More like this

Comparable products from verified suppliers

SITE Set delivery location
Home