About this product
Key features
- UL marked robust contactor design
- Compact size saving panel space
- Dual interlock between Mains and Gen (electrical and mechanical)
- Manual and remote reset provision
- Automatic generator start/stop
- Overload monitoring of generator supply
- Break before make changeover
- Coloured LED status indication
Specifications
Standard conformity: IEC 60947-6 | Versions: TPN/SPN & TPN/TPN | Mains current & voltage: 40A & 415 V~ (P-P) | Gen current & voltage: 6-40A & 230 V~ (P-N) & 6-40A & 415 V~ (P-P) | Frequency: 50 Hz | Rated impulse voltage: 6 kV | Duty: Continuous | Utilization category: AC32A | Conditional short circuit: 5 kA | Electrical life: 25000 ops. | Power consumption: <8 VA (Mains/GEN) | Protection: IP20 (terminal enclosure) | Pollution degree: III | Operating temperature: -5 to 55 C | Mounting: Panel mounting | Weight: 2.3 kg (unpacked) | Tripping accuracy: +/-5-10% of trip current | Timing accuracy: +/-5%
Standards: IEC 60947-6